Input
signals
|
Thermocouples |
B, R,
S, K, E, J, T, WWRe5-26, WWRe0-26, Ni-NiMo, AuFe-Cr,
N, PR5-20, PR20-40,
Platinel, U, L |
| DC
voltage |
±10mV,
±20mV, ±50mV, ±100mV, ±5V
|
| DC
current |
±20mA
|
| Resistance
thermometers |
Pt100,
JPt100, Pt50, Pt-Co
|
| Accuracy
rating |
±
0.1% of input span ± 1 digit or 10µV,
whichever is larger
(With thermocouple inputs,
reference junction temperature compensation accuracy
is not included.)
|
| Reference
temperature compensation accuracy |
±0.5°C
|
| Sampling
period |
About 0.1 second |
| Burnout |
Upscale
burnout for thermocouple and mV inputs |
| Output
at burnout |
Optional
set value: between -5% and 105% of control output |
| At
burnout |
High
alarm activation |
| Scaling |
DC
voltage and DC current inputs: Optional scaling
within 4 digits |
| Displays |
1st
display part: 7-segment back-lit LCD
2nd display
part: Full dot-matrix (96 x 20 dots) back-lit LCD
Adjustable angle of
viewing (± 20 degrees) |
| Power
supply |
85
to 264VAC, 50/60Hz (universal power supply) |
| Ambient
temperature |
-10
to 50°C |
| Ambient
humidity |
Less
than 90%RH (no dew condensation) |
| Power
consumption |
100VAC
maximum 15VA, 200VAC maximum 20VA |
| Weight |
About
750g (about 900g for models with full options) |
| Program
pattern setting system |
Key
switch setting |
| Number
of program pattern steps |
Maximum
19 steps/pattern |
| Number
of program patterns |
Maximum 19 patterns |
| Number
of program pattern repetitions |
Maximum
9999 times |
| Number
of program step repetitions |
Maximum
99 times |
| Parameters
to be selected for each step |
PID
constants (8 types, SV section automatic switching),
Alarm (8 types x 4 points), Output limiter (high
and low limits, 8 types), Output variation limit
(8 types), Actual temperature compensation (8 types),
Waiting time alarm (8 types), Sensor compensation
(8 types), Time signals (total 10 types: 8 types,
all OFF and all ON) |
| Control
switching cycle |
About
0.1 second |
| Control
system |
Current
output type PID, On-off pulse type PID, SSR drive
pulse type PID, On-off servo type PID, Voltage output
type PID (option) |
| Auto
tuning |
Provided.
PID constants can also be set manually. |
| PID
constants |
Settings
for each of 8 set values are possible.
P: 0 to 999.9% (0 for
on/off control)
I: 0 to 9999 seconds
(0 for without reset action)
D: 0 to 9999 seconds
|
| Anti-reset
windup |
Setting
of reset action: High 0 to 50.0%, Low (-) 50 to
0% |
| Current
output type PID |
Output
signal: 4 to 20mADC
Load resistance:
Less than 750
|
| On-off
pulse type PID |
Output
signal |
On-off
pulse conductive signal |
| Contact
capacity |
Resistive
load: 100VAC less than 2A, 200VAC less than 1A
Inductive load: 100VAC
less than 1A, 200VAC less than 0.5A
Minimum load: more than
5VDC 10mA |
| Alarm
points |
On-off
pulse period |
Variable between about 1 to 180 seconds |
| SSR
drive pulse PID |
Output
signal |
On-Off pulse voltage signal
ON: 12VDC ± 10% (maximum 20mA)
OFF: Less than 0.6VDC |
| On-off
pulse period |
Variable
between about 1 to 180 seconds |
| Contact
protective element |
Not
built-in (sold separately) |
| On-off
servo type PID |
Output
signal |
On-off servo conductive signal |
| Contact
capacity |
Inductive
load: 100VAC 1A, 200VAC 0.5A |
| Feedback
resistance |
100 to
2k |
| Load
current |
Standard: Maximum 1A, minimum 20mA
Light load: Maximum 2mA, minimum ImA |
| Alarm
points |
4 points for each control set point |
| Alarm
system |
High/low
alarms and deviation/absolute-value alarms
With standby function, independent setting for each
set value. |
| Alarm
outputs |
Transistor
open-collector output (maximum load 24VDC, 50mA) |
| Communications
interface |
RS-232C,
RS-422A (option) |
| CE
(option) |
EN61326
+ A1 Class A, EN61000-3-2 + A14
EN61000-3-3, EN61010-1 + A2 |