Controllers Indicators
Digital Program Setters
|
 |
 |
|
 |
|

|
KP3000 Series
Digital Program Setters
|
|
|
|
| The KP3000 series
is high-function digital program setters. The digital
program setters are used with existing ON-OFF controllers
or PID type controllers. The
output signals are digital signal (RS-422A) and analog
signals (4 to 20mADC, 0 to 1VDC, 0 to 10VDC and voltage
signal-equivalent to electromotive force of thermocouples).
|
 |
Features
- 19 program patterns
Maximum 19 program patterns, each
consisting of maximum 19 steps, can be stored in memory.
- Excellent operability,
clear graphic display
A full dot-matrix color LCD with
back-lit illumination displays the pattern of the
step being executed as well as the steps before and
after it. Parameters are set by interactive operation
for easy access to the many advanced functions.
- Free program pattern
linkage and repetition
Flexible pattern configurations including partial
pattern repetition, pattern linkage or whole pattern
repetition
- Versatile display showing
progress of process
The executing pattern and one of
the elapsed time of the pattern, the remaining time
of the pattern, the elapsed time of the step or the
remaining time of the step, are displayed. The displays
are accompanied by real-time bargraph displays so
you can check progress at a glance.
- CE (option)
Models complying with CE are available.
|
|
Models
|
Models
|
Output
signals
|
| KP3-10B000
|
Digital
output: RS-422A |
| KP3-20B000
|
Current
output: 4 to 20mA |
| KP3-30B000
|
Output
equivalent to electromotive force of thermocouples |
| KP3-40B000
|
Voltage
output: 0 to 10VDC |
| KP3-50B000
|
Voltage
output: 0 to 1VDC |
Outputs
|
Output
signals
|
Output
ranges
|
| Thermocouples
|
R
|
0 to
1760°C
|
| S
|
0 to
1760°C
|
| B
|
0 to
1820°C
|
| K
|
-200
to 1370°C
|
| E
|
-270
to 1000°C
|
| J
|
-200
to 1200°C
|
| T
|
-270
to 400°C
|
| N
|
0 to
1300°C
|
| WWRe5-26
|
0 to
2320°C
|
| WWRe0-26
|
0 to
2320°C
|
| PR20-40
|
0 to
1880°C
|
| PR5-20
|
0 to
1800°C
|
| Ni-NiMo
|
0 to
1310°C
|
| AuFe-Cr
|
0 to
300 K
|
| Platinel
|
-100
to 1390°C
|
| U
|
-200
to 400°C
|
| L
|
-200
to 900°C
|
| DC
voltage |
0 to
1 V, 0 to 10V
|
| DC
current |
4 to
20mA
|
Specifications
|
Display
|
| Display
1 |
SV value display (4-digit digital display
and engineering unit display), execution pattern
step No. display (2-digit display), set mode
display, running status display |
| Display
2 |
Graphic
display of pattern and digital/bargraph displays
of time in the operation mode. Display of
mode setting contents in setting mode |
|
| Program
pattern setting system |
Key
switch setting |
| Number
of program pattern steps |
Maximum19
steps/pattern
|
| Number
of program patterns |
Maximum 19 patterns |
| Number
of program pattern repetitions |
Maximum
9999 times |
| Number
of program step repetitions |
Maximum 99 times |
| Setting
range |
Temperature:
Refer to "Output" above.
DC voltage, current:
Arbitrary if not more than 4 digits
Time: 0 to 999 hours/59
minutes (resolution 1 minute) |
| Output
signal |
Linear
output: 4 to 20mADC, 0 to 1VDC, 0 to 10VDC
Voltage corresponding
to electromotive force of thermocouples |
| Output
updating period |
0.5
second |
| Output
resolution |
About
1/30000 |
| Power
supply |
85 to 264VAC, 50/60Hz
(universal power supply) |
| Ambient
temperature |
-10 to 50°C |
| Ambient
humidity |
Less than 90%RH (no dew condensation) |
| Power
consumption |
100VAC
maximum 15VA, 200VAC maximum 20VA |
| Weight |
About
750g (about 900g for models with full options) |
| CE
(option) |
EN61326
+ A1 Class A, EN61000-3-2 + A14
EN61000-3-3, EN61010-1 + A2 |
Other
specifications are the same as KP1000
series.