Thyristor
Regulators
Thyristor
Regulators |
 |
 |
|
 |
|

|
JS/JT Series
Thyristor Regulators
|
|
|
|
|
The JS/JT series is small
and lightweight thyristor regulators with built-in firing
unit for high density of mounting on instrumentation
panels.
Features
- Wide selection from
10A to 1000A on both single-phase and three-phase
load applications
- Two control systems
of phase-angle firing system and zero-cross firing
system
- 4 kinds of feedback
type of voltage feedback, current feedback, power
feedback and without feedback are available in accordance
with the characteristics of heating element on the
phase-angle firing system
- Two kinds of zero-cross
firing system, conventional type and

modulation type, are available for sensitive power
control
- Protection functions
including thyristor gate-off and rapid fuse are built-in.
|
|
Models
| Control
systems/Feedback systems |
Single-phase |
3-phase |
Power
voltage
100V |
Power
voltage
200V |
Power
voltage
400V |
Power
voltage
100V |
Power
voltage
200V |
Power
voltage
400V |
| Phase-angle
firing/Voltage feedback |
JS-1  V |
JS-2  V |
JS-4  V |
JT-1  V |
JT-2  V |
JS-4  V |
| Phase-angle
firing/Current feedback |
JS-1  A |
JS-2  A |
JS-4  A |
JT-1  A |
JT-2  A |
JS-4  A |
| Phase-angle
firing/Power feedback |
JS-1  W |
JS-2  W |
JS-4  W |
JT-1  W |
JT-2  W |
JS-4  W |
| Phase-angle
firing/Without feedback |
JS-1  N |
JS-2  N |
JS-4  N |
JT-1  N |
JT-2  N |
JS-4  N |
| Zero-cross
firing/Conventional type |
|
|
|
JT-1  Z |
JT-2  Z |
JS-4  Z |
Zero-cross
firing/ modulation
type |
JS-1  C |
JS-2  C |
JS-4  C |
|
|
|
Rated current: The above  specifies
the rated current. (ex. 010 for 10A)
10A: 010, 20A: 020, 30A: 030, 50A: 050, 75A: 075, 100A:
100, 150A: 150, 200A: 200,250A: 250, 300A: 300, 400A:
400, 500A: 500, 750A: 750, 1000A: X00
Specifications
| Rated
voltage |
100V/110V/120V,
200V/220V/240V, 380V/400V/440V AC (to be specified) |
| Frequency |
50/60Hz
(selected by terminal) |
| Rated
current |
14 kinds
of 10A, 20A, 30A, 50A, 75A, 100A, 150A, 200A, 250A,
300A, 400A, 500A, 750A, and 1000A (Reference: Ambient
temperature of 50°C) |
| Input
signal |
3 kinds
of 4 to 20mADC, 1 to 5mADC, and ON-OFF contact signal
(selected by terminal) |
| Input
resistance |
4 to
20mADC: less than 100 ,
1 to 5mADC: less than 400 |
| Output
range |
Phase-angle
firing system
|
Voltage
feedback type: 0 to 98% (95%) of rated voltage
Current feedback type:
0 to 100% of rated current
Maximum voltage output:
98% (95%) of rated voltage
Power feedback type:
0 to 98% (95%) of rated voltage x 0 to 100% of rated
current
Without feedback: 0
to 98% (95%) of rated voltage
|
Zero-cross
firing system
|
Conventional
type: 0 to 100% of rated voltage, Frequency division
cycle: 1.5 second

modulation type: 0 to
100% of rated voltage
The figures in ( ) indicate
the output for 3-phase control. |
| Load
applicable |
Resistive
load and inductive load (Primary side control of
transformer)
Resistive load only
for frequency division control system |
| Allowable
voltage fluctuation |
85 to
110% of rated voltage |
| Operating
temperature range |
Performance
guarantee range: 0 to 50°C
Operation guarantee
range: -50 to 50°C |
| Cooling
system |
Self-cooling
(Rated current: Single-phase - less than 150A. 3-phase
- less than 75A)
By built-in cooling
fan (Rated current: Single-phase - more than 200A.
3-phase - more than 100A) |
| Over
current protection |
Thyristor
gate off
Over current protection
function is not available for phase control system
without feedback, but the current transformer (CT)
for detecting current is sold separately. |
| Alarm |
Over
current alarm (on mounting CT for detecting current),
Rapid fuse melting (more than 30A)
Cooling fan abnormal
(Single-phase: more than 200A, 3-phase: more than
1150A): Contact output, lamp indication
Load disconnection alarm
(
modulation type only): Lamp indication |
| Accessories |
Variable
resistor (10k )for
gradient setting or low limit setting
Variable resistor (2k )for
manual setting, high limit setting or for elevation
Variable resistor (10k ,
2k )for
high limit setting and low limit setting
Variable resistor (10k ,
2k )for
output indicator, gradient setting/manual setting
and selection switch |
Page Top BACK
|
|
|
|