DZ2000 Series Digital Indicating Controllers
CHINO Japanese Page
Home Products Corporate Infomation Downloads Request Catalog


ControllersIndicators
Digital Indicating Controllers

DZ2000 Series Digital Indicating Controllers

 

 

The DZ2000 series is digital indicating controllerS having a feature to switch two groups of control setpoints by a front key. It can set PID constants, alarm setting, and other various parameters individually to two groups of setpoints. This easy-to-operate digital indicating controller is combined with auto tune and fuzzy logic.

Features
  • Easy operation and reliable control
    Owing to the universal inputs, selectable control outputs, auto tune, fuzzy logic and other features, thiscontroller ensures simplified control and easy operation. The setting of parameters and operation are easy.
  • Dust-proof and water-proof structure conforming to IP65
    The front operation panel is constructed to be dust-proof and water-protection to conform to IP65 of IEC standards (IEC529).
  • Two groups of control setpoints
    Two groups of control setpoints can be set, and PID constants, events, and other various parameters can be set individually to individual setting.
  • Simple program control
    Program control can be done easily by hold time of two groups of control setpoints and ramp setting (up and down) of the setpoints switching-change time.
  • CE (option)
    Models complying with CE are available. (for 24 VDC power supply only)

Models

Models

Control systems

DZ2010-000 On-off pulse type PID
DZ2020-000 On-off servo type PID
DZ2030-000 Current output type PID
DZ2050-000 SSR drive pulse type PID
DB20U0-000 Multi control output type
(On-off pulse type/ Current output type/ SSR drive pulse type)

Measuring ranges

Input signals

Measuring ranges

Thermocouples R

0 to 1760°C

S

0 to 1760°C

B

0 to 1820°C

K

-200 to 1370°C, -200 to 500°C

E

-270 to 700°C

J

-200 to 900°C

T

-200 to 400°C

N

0 to 1300°C

U

-200 to 400°C

L

-200 to 900°C

DC voltage

-20 to 20mV, -5 to 5V

DC current

0 to 20mA

Resistance thermometers Pt100

-200 to 660°C, -200 to 200°C

JPt100

-200 to 649°C, -200 to 200°C

Pt50

-200 to 649°C

Specifications
Input signals Thermocouples B, R, S, K, E, J, T, U, L
DC voltage ±20mV, ±5V
DC current 0 to 20mA
Resistance thermometers Pt100, JPt100, Pt50
Accuracy rating ±0.3% of input span ± 1 digit
Measuring unit °C or °F (by internal switch)
Sampling period About 0.2 second
Burnout Upscale burnout for thermocouple, mV and resistance thermometer inputs
At burnout Output 0% and high alarm activation
Measuring input shift (sensor correction) -200 to 1000 times of setting resolution
Scaling DC voltage and DC current inputs: Optional scaling for range and scale (-1999 to 9999)
Scaling decimal point 0 to 3
Displays 4-digit 2-stage display by 7-segment LED
9-item guide displays by individual LED
7-status displays by individual LED
(Event 2 points, AT, auto/manual display)
Display resolution Temperature input 0.1°C (maximum measuring input: less than 1000°C)
1°C (maximum measuring input: more than 1000°C)
DC voltage/current input 4-digit display (Decimal point and scaling are optional.)
Power supply 100 to 240VAC, 50/60Hz (universal power supply)
Ambient temperature -10 to 50°C
Ambient humidity 20 to 90%RH (no dew condensation)
Power interruption countermeasure Setting parameters are retained more than 10 years.
Allowable signal source resistance Thermocouple, DC voltage: less than 100ohm Resistance thermometer: less than 5ohm/wire (equal resistance for 3 wires)
Measuring current (resistance thermometer input) 2mA ± 20%
Power consumption Maximum 15VA
Front IEC529 IP65
Weight About 600g

Control Specifications
Control switching cycle About 0.2 second
Control system Current output type PID, On-off pulse type PID, SSR drive pulse type PID, On-off servo type PID, Multi control output type
Control set value 2 groups selection, Within the measuring range (-1999 to 9999)
Set value limit possible
Execution set values SV1ISV2 switching by front panel setting
Set value ramp function Two kinds of ramp values are settable for up ramp and down ramp of set values
Ramp unit of set values °C/min, °C/hour (l kind common to up ramp/down ramp)
Up ramp of set value 0 to 9999 (0 = Not operated)
Down ramp of set values 0 to 9999 (0 = Not operated)
PV start function At SV change (front panel, external signal), power on and MAN to AUTO switching (front panel, external signal) (External MAN, preset MAN)
ON/OFF switching is possible. (Engineering mode setting)
Control setting accuracy rating ±1 digit (relative error to indicating value)
Auto tuning Provided, PID constants can be also set manually.
PID constants Two groups switching by interlocking with SV (PID constants corresponding to the aimed setpoint No. are used during ramp operation of setpoints.)
P: 0.1 to 999.9%
I: 0 to 9999 seconds
D: 0 to 9999 seconds
ARW (anti-reset windup) High: 0.0 to 100.0%
Lower: (-) 100.0 to 0.0%
Fuzzy function Prevention of over-shoot by fuzzy calculation (ON-OFF setting possible)
Output limiter Two groups switching by interlocking with SV
High: 0.0 to 105.0%
Low: -5.0 to 100.0%
Output variable limiter 0.1 to 100.0%
Output deadband 0.1 to 9.9% (2-position control only)
Auto/manual output Balanceless bumpless
Manual output range -5.0 to 105.0% (0.1% increment)
Control action Direct action/reverse action selectable (by dip switches)
Current output type PID Output signal 4 to 20mADC
Load resistance Less than 600ohm
On-off pulse type PID Output signal On-off pulse conductive signal
Contact rating Resistive load 100VAC 2A, 200VAC 1A, 24VDC 1A
Inductive load 100VAC 1A, 200VAC 0.5A, 24VDC 0.5A
Minimum load 5VDC more than 10mA
On-off pulse period Variable between about 1 to 120 seconds
Contact protective element Not built-in (sold separately)
SSR drive pulse PID Output signal On-Off pulse voltage signal
ON: 12VDC ± 20% (maximum 20mA)
OFF: Less than 0.8VDC
On-off pulse period Variable between about 1 to 120 seconds
On-off servo type PID Output signal On-off servo conductive signal
Contact capacity Resistive load 100VAC 2A, 200VAC 1A
Inductive load 100VAC 1A, 200VAC 0.5A
Feedback resistance 100ohm to 2kohm
Contact protective element Not built-in (sold separately)

Event Specifications
Event points 2 points (EV1,EV2)
Event system Absolute value alarm: High/low limits, Standby function provided/not provided Deviation alarm: High/low limits, Standby function provided/not provided Output value alarm - High/low, Standby function provided/not provided Heater disconnection alarm (for pulse output type controllers with optional CT input only) SV status (ON during SV ramp, ON during SV no-ramp, Event set values are ineffective in this case.)
Event set values Two groups (PARA1, PARA2) are set to event outputs (EV1, EV2) individually.
Two groups (PARA1, PARA2) are switched by interlocking with SV.
Event deadband 1000 times of setting resolution from 0
Event output Output signal: Form A relay contact
Contact rating Resistive load 100VAC 2A, 200VAC 1A, 24VDC 1A Inductive load 100VAC 1A, 200VAC 0.5A, 24VDC0.51A Minimum load 5VDC more than 10mA
Contact protective element Not built-in (sold separately)

Simple Program Specifications
Program functions Simple program control can be executed by combining 2 groups of SV and setpoint ramp function with the internal hold time timer
Program patterns One of the following 4 kinds is selectively executed.
1-stage trapezoidal pattern/2-stage trapezoidal pattern/3-stage trapezoidal pattern/repetition of 2-stage trapezoidal pattern
Hold time 1/2/3 1 to 999 minutes
Program start/reset Front panel operation or external signal (option)
Program end Automatic switching to preset manual or fixed setpoint control
Preset manual setting range -5.0 to 105.0%

Other specifications are the same as DZ1000 series.