Models
|
Models
|
Specifications
|
| LT11010000-00A
|
Universal
input/On-off pulse type |
| LT11030000-00A
|
Universal
input/Current output type |
| LT11050000-00A
|
Universal
input/SSR drive pulse type |
| LT11110000-00A
|
Thermocouple
universal input/On-off pulse type |
| LT11130000-00A
|
Thermocouple
universal input/Current output type |
| LT11150000-00A |
Thermocouple
universal input/SSR drive pulse type |
Measuring Ranges
| Inputs |
Input
ranges |
| Thermocouple |
K |
0
to 1370°C |
0
to 2500°F |
| J |
0
to 1000°C |
0
to 1800°F |
| E |
0
to 800°C |
0
to 1500°F |
| Platinel
II |
0
to 1390°C |
0
to 2500°F |
| N |
0
to 1300°C |
0
to 2300°F |
| Resistance
thermometers |
Pt100 |
-199.9
to 850.0°C |
-199.9
to 999.9°F |
| -200 to 850°C |
-300 to 1500°F |
| JPt100 |
-199.9
to 500.0°C |
-199.9
to 900.0°F |
| -200 to 500°C |
-300 to 900°F |
Specifications
Input Specifications
| Input
signal |
| Thermocouple
|
K, N, J, E,
Platinel II |
Resistance thermometer
Pt100,
JPt100 |
| Accuracy
rating |
Thermocouple
input
±0.3% of input span ±
1 digit or ±2°C, whichever is larger
Resistance thermometer input
±0.2%
of input span ± 1 digit |
| Measuring
unit |
°C
or °F |
| Sampling
cycle |
About
0.25 second |
| Burnout |
Up
scale |
| Allowable
signal source resistance |
Thermocouple
inut
100
or lower
Resistance thermometer input
10
or lower per wire |
| Input
shift |
-100.0
to 100.0°C |
Control Specifications
| Control
cycle time |
Approx.
0.25 second |
| Control
system |
PID
(2-position control is available. |
| Control
setpoint |
2
sets switching, 4-digit setting |
| Auto-tuning |
Standard
(Manual setting of PID constants enabled) |
| PID
constants |
| P
|
0 to maximum
value of range |
| I
|
0 to 3600 seconds |
| D
|
1 to 3600 seconds |
|
| Control
gap |
0.1
to 100.0°C (2-position control only) |
| Anti-reset
windup |
Automatic |
| Output
specifications |
On-off pulse type
| |
Output signal |
|
On-off
pulse conductive signal |
| |
Contact ratings |
|
Resistive load: |
250VAC 3A |
| |
|
|
Inductive load: |
250VAC 1A |
| |
Pulse cycle |
|
Approx.
1 second to 120 seconds adjustable |
Current output type
| |
Output signal |
|
4
to 20mADC |
| |
Load resistance |
|
550
or less |
SSR drive pulse type
| |
Output signal |
|
On-off
pulse voltage signal
At ON 12VDC ± (0 to +2V) maximum 40mA |
| |
Pulse cycle |
|
Approx.
1 second to 120 seconds adjustable |
|
Alarm Specifications
| Alarm
point |
1
point |
| Temperature
alarm type |
Deviation
high alarm, deviation low alarm
Absolute value deviation high alarm, absolute value
deviation low alarm
Deviation high alarm with standby function
Deviation low alarm with standby function
Absolute value deviation high alarm with standby
function
Absolute value deviation low alarm with standby
function
Absolute value high alarm, absolute value low alarm
Absolute value high alarm with standby function
Absolute value low alarm with standby function |
| Loop
break alarm |
Alarm
activation when the control output is maximum or
minimum and the process value does not vary more
than a set band in a set time.
Heater disconnection, sensor disconnection, control
equipment failure
Alarm time setting range: 0 to 200 minutes
Alarm band: 0 to150°C or 0.0 to 150.0°C |
| Alarm
deadband |
0.1
to 100°C |
| Alarm
output |
Open
collector 24VDC 0.1A (maximum) |
Display Specifications
| Display |
4-digit
LED |
| Display
contents |
PV
or SV switching, Parameter item |
General Specifications
| Power
voltage |
100V
to 240VAC 50/60Hz universal power supply |
| Working
temperature range |
-10
to 50°C |
| Working
humidity range |
35
to 85%RH (no dew condensation) |
| Power
consumption |
Maximum
about 5VA |
| installation |
Panel
installation |
| Weight |
About
100g |
*PDF data sheet is available at
"Download Center".