Recorders / Loggers
Field
Data Scanning Units
|
 |
 |
|
 |
|
SE3000 Field
Data Scanning Units |
| |
|
SE3000 series scanning units
are designed for data logging with a personal computer.
The basic unit with 6 input points can be connected to
7 sub units (6 input points / sub unit) and maximum 48
analog data can be collected.
Two soft ware packages, "KIDS" for data logging and "PASS"
for parameter programming, are available.
|
 |
Features
- Expanded type units
can expand input points up to 48 points by connecting
sub units (6-point input).
- Data can be easily collected
by the data logging software package "KIDS" and the
parameter programming software package "PASS".
The "KIDS" can connect up to 5 sets of SE3000 and
manage up to 100 channels.
- 3 kinds of communications
interfaces of RS-232C, RS-422A and are built-in.
- The communications protocol
is MODBUS for easy system configuration.
- Universal input (32
kinds of DC voltage, thermocouples and resistance
thermometers)
- Input is isolated between
all channels.
- The unit can be used
with BR series graphic recorder as an input extension
unit (up to 24 points).
- CE conformance
|
Models
| Types |
Models |
| Base unit |
Without
display |
SE3100-000 |
| With display |
SE3101-000 |
| Sub unit |
SE3211-000 |
Specifications
| Measuring
point |
Base unit
6 points, sub unit 6-point/unit
* Up to 7 sub units can be connected to 1 base unit
(up to 48 points). |
| Input
kind |
Universal
input
10 DC voltage, 17 thermocouples, 5 resistance thermometers |
| Accuracy
rating |
±0.1%±
1digit (for DC voltage and thermocouples) |
| Measuring
cycle |
1 second
(for 6 points) to 8 seconds (for 48 points) |
| Burnout |
Sensor
disconnection judgment function of thermocouples
and resistance thermometer inputs is built-in. (Enable/disable
selectable) |
| Communications
interface |
RS-232C,
RS-422A, RS-485 (switch selection)
* MODBUS protocol |
| Alarm |
Up to
4 alarms for each channel |
| Alarm
type |
High,
low, differential high, differential low, rate-of-change
increase, rate-of change decrease (no alarm output) |
| Dimension |
Base unit
H138 x W72 x D100mm
Sub unit H138 x W36 x D100mm |
| Mounting |
DIN (35mm)
rail mounting |
| Rated
power voltage |
100V to
240VAC 50/60Hz |
Display Unit Specifications
(option, later mounting available)
| Display
unit |
7-segment
red LED 7 digits |
| Display
content |
Channel
number 2 digits, data 5 digits (channel forwarding/fixed)
|
| Display
renewal cycle |
3 seconds |
*PDF data sheet is available at
"Download Center".
Page Top
BACK
|
|
|
|