Recorders
/ Loggers
Analog Recorders |
 |
 |
|
 |
|
EL3000
Series Analog Recorders |
|
|
|
|
The EL3000 series is an alalog recorder sized
144 x 144mm with 100mm width chart.
The unit starts recording
as soon as the
power supply and
input are connected
and
it is also easy to
operate.
Scale plate, input
range and function of
the recorder can
be selected for various
purpose and applications
as many kinds of
options are prepared.

Features
- Universal power supply
- Alarm setting (common alarm) as standard
- Linear temperature scale
- CE marking
|
Models
| Input point |
Input signals |
| Thermocouple/DC voltage |
Resistance thermometer |
| Dot-printing type |
1point |
EL3D15-000 |
EL3D17-000 |
| 2point |
EL3D25-000 |
EL3D27-000 |
| 3point |
EL3D35-000 |
EL3D37-000 |
| 6point |
EL3D65-000 |
EL3D67-000 |
| Pen-writing type |
1-pen |
EL3P15-000 |
EL3P17-000 |
| 2-pen |
EL3F00N-00 |
| 3-pen |
EL3G000-00 |
Specifications
| Measuring
points
|
1-pen, 2-pen, 3-pen |
| 6
points |
| Input
signals |
Universal
input |
| R, S, K, E, J, T, B(option) |
| Pt100 |
| ±13.8mV, ±27.6mV, ±69.0mV,
±200mV,
±500mV,
±2V,±5V,
±10V,
±25V,
±50V |
| By
shunt resistor |
| Accuracy
rating |
±0.5% of input span |
| Measuring
cycle |
125ms |
| 6 seconds/point |
| Reference
junction compensation accuracy |
K, E, J, T--±1.0°C or less(23°C±10°C)
±2°C or less(0 to 50°C) |
| Burnout
|
On thermocouple and resistance thermometer
input,disconnection
of signal can
be detected |
| Printing
system |
Analog
tracing |
Disposal
cartridge pen |
| Digital
printing |
Plotter
pen |
| Wire-dotting
system 6-color ribbon |
| Printing
colors |
1st-pen red, 2nd-pen green, 3rd-pen blue |
| 1
red, 2 black, 3 blue, 4 green,
5 brown,
6 purple |
| Chart
|
Fan-fold
type, effective width 100mm,
total width
114mm,
total length 10m |
| Chart
speed |
6-speed change,5,10,20,40,80,160mm/h (standard) |
| Alarm
type |
Higher and lower-limit alarm |
| Rated
power voltage |
100
to 240VAC 50/60Hz, universal
power supply |
| Power
consumption |
Maximum 16VA(100V AC),Maximum 22VA(240V AC) |
| Maximum 12VA(100V AC),Maximum 20VA(240V AC) |
| Environmental
conditions |
Ambient temperature range: 21 to 25°C
Ambient humidity
range:45 to 65%RH
Power voltage:
100V AC ±1% |
| Mounting
|
Panel
mounting |
| Dimensions
|
W144 x H144 x D194mm (standard specifications) |
| Weight
|
About 1.6kg |
| About 1.7kg |
| Standards
|
EN61326 + A1 + A2 , EN61000-3-2
EN61000-3-3 + A1, EN61010-1 |
*PDF data sheet is available at
"Download Center".
Page Top