| Phase |
Three-phases |
| Rated voltage | 200V AC(200V/ 220V/ 240V selectable by switch)
400V AC(380V/ 400V/ 440V selectable by switch)
to be specified ( main circuit power supply
and control circuit power supply are common)
* The models which have a different main
circuit power supply and a control circuit
power supply are manufactureable. |
| Rated current | 10A, 20A, 30A, 50A, 75A, 100A, 150A, 200A,
250A, 300A,
400A, 500A,750A, 1000A to be
specified |
| Rated frequencies | 50/60 Hz (automatic change) |
| Control system | Phase angle firing system and zero-crossing
firing system |
| Feedback types | Voltage, current, power feedback |
| Control input signal | 4 to 20mA DC( input resistance is approx.
100Ω )
1 to 5V DC( input resistance is approx. 50kΩ ) |
| Current limit | 0 to 100 %of output range |
| Output range | 0 to 98 % of supplied power voltage |
| Applicable load | Resistive load, inductive load,
density 1.2 T or lower are recommended) |
| Minimum load current | 0.5 A or more( at 98% output of rated voltage) |
| Working temperature | -10 to 55°C
In case of more than 40°C it depends
on the following derating performance |
| Working humidity | 30 to 90 %RH, No dew-condensation |
| Weight | About 6kg for 10A and 20A
About 8kg for 30A and 50A
About 13kg for 75A and 100A
About 22kg for 150A to 250A,
About 36kg for 300 to 500A |